COAL MINING SAFETY AND HEALTH REGULATION 2017 - REG 242
Intake airways
242 Intake airways
(1) At least 1 automatic methane detector must be located in each intake
airway at the interface between— (a) a NERZ and ERZ1; and
(b) 2 NERZs.
Example of interface between 2 NERZs— the interface between subdivided
parts of a NERZ
(2) A detector located at an interface between a NERZ and
ERZ1 must— (a) when the general body concentration of methane detected at
the interface exceeds 0.25%—automatically activate a visible alarm; and
(b)
when the general body concentration of methane detected at the interface
exceeds 0.5%—automatically trip the electricity supply to non-intrinsically
safe plant in— (i) the ERZ1 and NERZ; or
(ii) if the NERZ has been
subdivided—the ERZ1 and the subdivided part of the NERZ adjacent to the
ERZ1.
(3) A detector located at the interface between a NERZ and an ERZ1 must
be a self-contained unit or part of the gas monitoring system for the mine.
(4) A detector located at an interface between 2 NERZs must— (a)
automatically activate a visible alarm when the general body concentration of
methane detected at the interface exceeds 0.25%; and
(b) if the NERZ has been
subdivided—automatically trip the electricity supply to non-intrinsically
safe plant in the adjacent subdivided part when the general body concentration
of methane detected at the interface exceeds 0.5%.
(5) The alarm mentioned in
subsection (2) (a) or (4) (a) must be visible at the interface.