116 Specified electrical equipment
(1) A person conducting a business or undertaking at a workplace must ensure
that specified electrical equipment of the person is not used to perform work
unless— (a) it is inspected and tested by a competent person— (i) if the
equipment is double insulated—at least once every year; or
(ii) if the
equipment is not double insulated—at least once every 6 months; and
(b) it
is connected to a type 1 safety switch or type 2 safety switch.
(2) If after
inspecting and testing the electrical equipment under subsection (1) (a) , a
competent person decides the equipment is safe to use, the person conducting
the business or undertaking must ensure the competent person immediately
attaches a durable tag to the equipment that shows the prescribed details for
the equipment.
(3) If after inspecting and testing the electrical equipment
under subsection (1) (a) , a competent person decides the equipment is not
safe to use, the person conducting the business or undertaking must ensure—
(a) the competent person immediately attaches a durable tag to the equipment
that warns people not to use the equipment; and
(b) the equipment is
immediately withdrawn from use.
(4) The person conducting the business or
undertaking must ensure that, for the purposes of the business or undertaking,
a tag is not attached to specified electrical equipment under subsection (2)
unless— (a) the equipment is new; or
(b) both of the following apply— (i)
the equipment has been inspected and tested by a competent person;
(ii) the
tag was attached by the competent person.
Note for subsections (1) to (4)—
ES Act — section 30 (see section 8 )