ELECTRICAL SAFETY REGULATION 2013 - SCHEDULE 2

SCHEDULE 2 – Exclusion zones for overhead electric lines

Part 1 - Preliminary

1 Definitions for sch 2

In this schedule—

"another safe system" , for the operation of operating plant, means a system of work that—

(a) has been developed in consultation with persons who are broadly representative of industrial organisations of employees whose members commonly operate operating plant of the operating plant’s type; and
(b) provides, for persons and property, the same level of electrical safety as, or a greater level of electrical safety than, the level of electrical safety provided with a safety observer.

"authorised person" , for an electric line, means a person who—
(a) has enough technical knowledge and experience to do work that involves contact with, or being near to, the electric line; and
(b) has been approved by the person in control of the electric line to do work that involves contact with, or being near to, the electric line, or is authorised to act for the person in control of the electric line.

"instructed person" , for an electric line, means a person who is acting under the supervision of an authorised person for the electric line.

"untrained person" , for an electric line, means a person who is not an authorised person or an instructed person for the electric line.

2 Authorised persons and instructed persons taken to be untrained persons in particular circumstances

(1) This section applies if operating plant is operated by an authorised person or instructed person, for an electric line, who does not have a safety observer or another safe system as required under this schedule.
(2) The operating plant is taken to be operated by an untrained person for the electric line.

3 Exclusion zones for operating plant fitted with certain safety devices

(1) This section applies if—
(a) operating plant, operated by an authorised person or instructed person for an electric line, is fitted with a device capable of stopping the operation of the plant immediately when the operating plant is at the exclusion zone for an authorised person or instructed person for the electric line; and
(b) a safe system of work for the use of the operating plant is in place; and
(c) the safe system of work has been developed in consultation with persons who are broadly representative of industrial organisations of employees whose members commonly operate operating plant of the operating plant’s type; and
(d) without limiting paragraph (b) , the safe system of work ensures the device mentioned in paragraph (a)
(i) is operating properly; and
(ii) is set for at least the correct exclusion zone distance.
(2) The exclusion zone for an authorised person or instructed person for the electric line applies as the exclusion zone for the operating plant for the electric line.

Part 2 - Overhead uninsulated electric lines

Division 1 - Exclusion zones for untrained persons

Nominal phase to phase voltage of overhead uninsulated electric line Untrained person for the electric line (mm) Operating plant operated by untrained person for the electric line (mm) Vehicle operated by untrained person for the electric line (mm)
low voltage (with consultation with person in control of electric line) 1,000 3,000 600
low voltage (without consultation with person in control of exposed electric line) 3,000 3,000 600
above low voltage, up to 33kV (with consultation with person in control of exposed electric line) 2,000 3,000 900
above low voltage, up to 33kV (without consultation with person in control of electric line) 3,000 3,000 900
above 33kV up to 132kV 3,000 3,000 2,100
above 132kV up to 220kV 4,500 6,000 2,900
above 220kV up to 275kV 5,000 6,000 2,900
above 275kV up to 330kV 6,000 6,000 3,400
above 330kV up to 500kV 6,000 8,000 4,400

Nominal pole to earth dc voltage of exposed electric line Untrained person for the electric line (mm) Operating plant operated by untrained person for the electric line (mm) Vehicle operated by untrained person for the electric line (mm)
+/- 25kV 3,000 3,000 900
+/- 85kV 3,000 3,000 2,100
+/- 150kV 3,000 3,000 2,100
+/- 270kV 4,500 6,000 2,900
+/- 350kV 5,000 6,000 2,900
+/- 400kV 6,000 6,000 3,400

Division 2 - Exclusion zones for authorised or instructed persons

Nominal phase to phase voltage of overhead uninsulated electric line Authorised person or instructed person for the electric line (mm) Operating plant operated by authorised person or instructed person for the electric line, with safety observer or another safe system (mm) Vehicle operated by authorised person or instructed person for the electric line (mm)
low voltage (no exclusion zone prescribed) 1,000 600
above low voltage, up to 33kV 700 1,200 700
above 33kV up to 50kV 750 1,300 750
above 50kV up to 66kV 1,000 1,400 1,000
above 66kV up to 110kV 1,000 1,800 1,000
above 110kV up to 132kV 1,200 1,800 1,200
above 132kV up to 220kV 1,800 2,400 1,800
above 220kV up to 275kV 2,300 3,000 2,300
above 275kV up to 330kV 3,000 3,700 3,000
above 330kV up to 400kV 3,300 4,000 3,300
above 400kV up to 500kV 3,900 4,600 3,900

Nominal pole to earth dc voltage
of exposed electric line
Authorised person or instructed person for the electric line (mm) Operating plant operated by authorised person or instructed person for the electric line, with safety observer or another safe system (mm) Vehicle operated by authorised person or instructed person for the electric line (mm)
+/- 25kV 700 1,200 700
+/- 85kV 1,000 1,800 1,000
+/- 150kV 1,200 1,800 1,200
+/- 270kV 1,800 2,400 1,800
+/- 350kV 2,500 3,200 2,500
+/- 400kV 2,900 3,600 2,900

Part 3 - Overhead insulated electric lines

Division 1 - Exclusion zones for untrained persons

Nominal phase to phase voltage of overhead insulated electric line Untrained person for the electric line (mm) Operating plant operated by untrained person for the electric line (mm) Vehicle operated by untrained person for the electric line (mm)
low voltage (with consultation with, and with insulation verified by, an authorised person for the electric line) (No exclusion zone prescribed) 1,000 300
low voltage (without consultation with, and without insulation verified by, an authorised person for the electric line) 3,000 3,000 600
above low voltage, up to 33kV (with consultation with person in control of electric line) 2,000 3,000 900
above low voltage, up to 33kV (without consultation with person in control of electric line) 3,000 3,000 900
above 33kV up to 66kV 3,000 3,000 2,100
Nominal pole to earth dc voltage of electric line
+/- 25kV 3,000 3,000 900
+/- 85kV 3,000 3,000 2,100

Division 2 - Exclusion zones for authorised or instructed persons

Nominal phase to phase voltage of overhead insulated electric line Authorised person or instructed person for the electric line (mm) Operating plant operated by authorised person or instructed person for the electric line, with safety observer or another safe system (mm) Vehicle operated by authorised person or instructed person for the electric line (mm)
low voltage (with consultation with, and with insulation verified by, an authorised person for the electric line) (no exclusion zone prescribed) (no exclusion zone prescribed) (no exclusion zone prescribed)
low voltage (without consultation with, and without insulation verified by, an authorised person for the electric line) (no exclusion zone prescribed) (no exclusion zone prescribed) 600
above low voltage, up to 33kV (with consultation with person in control of electric line) 700 700 700
above low voltage, up to 33kV (without consultation with person in control of electric line) 700 700 700
above 33kV up to 50kV 750 750 750
Above 50kV up to 66kV 1,000 1,000 1,000
Nominal pole to earth dc voltage of electric line
+/- 25kV 700 700 700
+/- 85kV 1,000 1,000 1,000