ELECTRICAL SAFETY REGULATION 2013 - SCHEDULE 4

SCHEDULE 4 – Clearance of overhead electric lines (other than low voltage service lines)

Part 1 - Low voltage conductor clearance—from ground

Vertical clearance from roads
1 The minimum vertical clearance from roads must be, in all positions and whether or not insulated 5.5m
Vertical clearance from other than roads
2(1) The minimum vertical clearance from other than roads must be, whether or not insulated 5.5m
(2) This item does not apply if item 3 or 4 applies.
Vertical clearance over nontrafficable land
3 The minimum vertical clearance over land that, because of the steepness or swampiness of its terrain, can not be crossed by traffic or mobile machinery, must be, whether or not insulated 4.5m
Horizontal clearance from road cuttings and embankments
4 The minimum horizontal clearance, whether or not insulated, in accordance with note 2, from road cuttings, embankments and similar features must be, whether or not insulated 1.5m

Part 2 - Low voltage conductor clearance—from structures

Clearance from unroofed terraces, balconies and sun decks
1 The minimum clearance, in accordance with note 2, for unroofed terraces, balconies, sun decks, paved areas and similar areas that are subject to pedestrian traffic only, that have a surrounding hand rail or wall and on which a person is likely to stand must be—
(a) vertically—
(i) insulated 2.7m
(ii) uninsulated 3.7m
(b) horizontally—
(i) insulated 1.2m
(ii) uninsulated 1.5m
Clearance from roofs or similar structures not used for traffic
2 The minimum clearance vertically and horizontally, in accordance with note 2, for roofs or similar structures not used for traffic or resort but on which a person is likely to stand, and for parapets surrounding roofs or similar structures not used for traffic or resort but on which a person is likely to stand, must be—
(a) vertically—
(i) insulated 2.7m
(ii) uninsulated 3.7m
(b) horizontally—
(i) insulated 0.9m
(ii) uninsulated 1.5m
Clearance from covered places of traffic
3 The minimum clearance in any direction from covered places of traffic or resort, including, for example, windows capable of being opened, roofed open verandahs and covered balconies, must be—
(a) insulated 1.2m
(b) uninsulated 1.5m
Horizontal clearance from blank walls or windows
4 The minimum clearance horizontally from blank walls or windows that can not be opened must be—
(a) insulated 0.6m
(b) uninsulated 1.5m
Clearance from structures not normally accessible to persons
5 The minimum clearance from other structures not normally accessible to persons must be, in accordance with note 2—
(a) vertically—
(i) insulated 0.6m
(ii) uninsulated 2.7m
(b) horizontally—
(i) insulated 0.3m
(ii) uninsulated 1.5m

Part 3 - High voltage conductor clearance—from ground

Vertical clearance from roads
1 The minimum vertical clearance from roads must be—
(a) crossing the carriageway—
(i) more than 1,000V but not more than 132kV 6.7m
(ii) more than 132kV but not more than 275kV 7.5m
(iii) more than 275kV but not more than 330kV 8.0m
(iv) more than 330kV but not more than 500kV 9.0m
(b) at other places—
(i) more than 1,000V but not more than 33kV 5.5m
(ii) more than 33kV but not more than 132kV 6.7m
(iii) more than 132kV but not more than 275kV 7.5m
(iv) more than 275kV but not more than 330kV 8.0m
(v) more than 330kV but not more than 500kV 9.0m
Vertical clearance from other than roads
2(1) The minimum vertical clearance from other than roads must be—
(a) more than 1,000V but not more than 33kV 5.5m
(b) more than 33kV but not more than 132kV 6.7m
(c) more than 132kV but not more than 275kV 7.5m
(c) more than 275kV but not more than 330kV 8.0m
(e) more than 330kV but not more than 500kV 9.0m
(2) This item does not apply if item 3 or 4 applies.
Vertical clearance over nontrafficable land
3 The minimum vertical clearance over land that, because of the steepness or swampiness of its terrain, can not be crossed by traffic or mobile machinery must be—
(a) more than 1,000V but not more than 33kV 4.5m
(b) more than 33kV but not more than 132kV 5.5m
(c) more than 132kV but not more than 275kV 6.0m
(d) more than 275kV but not more than 330kV 6.7m
(e) more than 330kV but not more than 500kV 7.5m
Horizontal clearance from road cuttings and embankments etc.
4 The minimum horizontal clearance, in accordance with note 2, from road cuttings, embankments and other similar places must be—
(a) more than 1,000V but not more than 33kV 2.1m
(b) more than 33kV but not more than 132kV 4.6m
(c) more than 132kV but not more than 275kV 5.5m
(d) more than 275kV but not more than 330kV 6.0m
(e) more than 330kV but not more than 500kV 7.0m

Part 4 - High voltage conductor clearance—from structures

Clearance from unroofed terraces, balconies and sun decks
1 The minimum clearance, in accordance with note 2, for unroofed terraces, balconies, sun decks, paved areas and similar areas that are subject to pedestrian traffic only, that have a surrounding hand rail or wall and on which a person is likely to stand, must be—
(a) vertically—
(i) more than 1,000V but not more than 33kV 4.6m
(ii) more than 33kV but not more than 132kV 5.5m
(iii) more than 132kV but not more than 275kV 6.5m
(iv) more than 275kV but not more than 330kV 7.0m
(v) more than 330kV but not more than 500kV 8.0m
(b) horizontally—
(i) more than 1,000V but not more than 33kV 2.1m
(ii) more than 33kV but not more than 132kV 4.6m
(iii) more than 132kV but not more than 330kV 5.5m
(iv) more than 330kV but not more than 500kV 6.0m
Clearance from roofs or similar structures not used for traffic
2 The minimum clearance vertically and horizontally, in accordance with note 2, for roofs or similar structures not used for traffic or resort but on which a person is likely to stand, and for parapets surrounding roofs or similar structures not used for traffic or resort but on which a person is likely to stand, must be—
(a) vertically—
(i) more than 1,000V but not more than 33kV 3.7m
(ii) more than 33kV but not more than 132kV 4.6m
(iii) more than 132kV but not more than 275kV 6.0m
(iv) more than 275kV but not more than 330kV 6.5m
(v) more than 330kV but not more than 500kV 7.5m
(b) horizontally—
(i) more than 1,000V but not more than 33kV 2.1m
(ii) more than 33kV but not more than 132kV 4.6m
(iii) more than 132kV but not more than 330kV 5.5m
(iv) more than 330kV but not more than 500kV 6.0m
Clearance from covered places of traffic
3 The minimum clearance in any direction from covered places of traffic or resort such as windows capable of being opened, roofed open verandahs and covered balconies must be—
(a) more than 1,000V but not more than 33kV 2.1m
(b) more than 33kV but not more than 132kV 4.6m
(c) more than 132kV but not more than 330kV 5.5m
(d) more than 330kV but not more than 500kV 6.0m
Horizontal clearance from blank walls or windows
4 The minimum clearance horizontally from blank walls or windows that can not be opened must be—
(a) more than 1,000V but not more than 33kV 1.5m
(b) more than 33kV but not more than 66kV 3.0m
(c) more than 66kV but not more than 132kV 4.6m
(d) more than 132kV but not more than 330kV 5.5m
(e) more than 330kV but not more than 500kV 6.0m
Clearance from structures not normally accessible to persons
5 The minimum clearance from other structures not normally accessible to persons must be, in accordance with note 2—
(a) vertically—
(i) more than 1,000V but not more than 66kV 3.0m
(ii) more than 66kV but not more than 132kV 4.6m
(iii) more than 132kV but not more than 330kV 5.5m
(iv) more than 330kV but not more than 500kV 6.0m
(b) horizontally—
(i) more than 1,000V but not more than 33kV 1.5m
(ii) more than 33kV but not more than 66kV 3.0m
(iii) more than 66kV but not more than 132kV 4.6m
(iv) more than 132kV but not more than 330kV 5.5m
(v) more than 330kV but not more than 500kV 6.0m
Note 1—
For this schedule, a conductor is taken to be insulated if it is insulated in accordance with AS/NZS 5000.1 (Electric cables—Polymeric insulated—For working voltages up to and including 0.6/1 (1.2) kV) or AS/NZS 3560.1 (Electric cables—Cross-linked polyethylene insulated—Aerial bundled—For working voltages up to and including 0.6/1(1.2)kV). Otherwise, it is taken to be uninsulated.
Note 2—
Either the vertical clearance or the horizontal clearance stated must be maintained. Also, in the zone outside the vertical alignment of the building, road cutting, embankments and similar places, either the horizontal clearance from the vertical alignment or the vertical clearance from the horizontal level on which a person is likely to stand must be maintained.