South Australian Numbered Regulations

[Index] [Table] [Search] [Search this Regulation] [Notes] [Noteup] [Previous] [Next] [Download] [Help]

ELECTRICITY (GENERAL) REGULATIONS 2012 (NO 199 OF 2012) - SCHEDULE 1

Schedule 1—Requirements for aerial lines

(Regulation 48)

1—Interpretation

In this Schedule—

listed standards means the standards (both national and international), codes, guides and other documents, as published from time to time, listed in the Appendix at the end of this Schedule;

maximum design temperature means the maximum temperature that conductors may reach under the influence of load current (excluding fault current), ambient temperature of the air and solar radiation.

2—Design

Aerial lines must be designed so that the lines—

            (a)         have safe levels of electrical insulation; and

            (b)         will carry the electrical load currents for which they are designed without failure; and

            (c)         will allow the passage of electrical short circuit currents which will enable the correct operation of protective devices; and

            (d)         are structurally secure for the environmental and service conditions for which they are designed; and

            (e)         maintain safe clearances,

so as to comply with the listed standards or achieve, to the satisfaction of the Technical Regulator, the same or better safety and technical outcomes.

3—Materials

Aerial line structures, their components, conductors, cables and accessories must, so as to ensure safe operational performance, conform to the listed standards or achieve, to the satisfaction of the Technical Regulator, the same or better safety and technical outcomes.

4—Thermal ratings

        (1)         The thermal capacity of a conductor must be sufficient to pass the electrical load for which it is designed without losing any mechanical properties that would affect the safety of the line.

        (2)         Thermal ratings of conductors must be determined in accordance with the guidelines set out in the listed standards.

5—Short circuit ratings

        (1)         The conductors of aerial lines must be of sufficient size to pass short circuit currents so as to enable the correct operation of protective devices without losing any mechanical properties that would affect the safety of the line.

        (2)         Short circuit capacity of conductors must be determined in accordance with the guidelines set out in the listed standards.

6—Mechanical loading conditions

        (1)         The mechanical loads used for the design of aerial lines must be based on the local environment and electrical service conditions.

        (2)         In determining electrical service conditions and the physical environment under which the line will operate, due care must be given to the consideration of extremes that may occur, the likelihood of their occurrence and the associated risks.

        (3)         Mechanical loading conditions must be determined in accordance with the guidelines set out in the listed standards.

7—Conductor tensions

        (1)         The conductors for use with aerial lines must be designed to withstand the mechanical loads determined for their operation over the designed operational life of the line.

        (2)         Conductors for lines must be designed so as to comply with the listed standards or achieve, to the satisfaction of the Technical Regulator, the same or better safety and technical outcomes.

8—Structures and footings

        (1)         The structures and footings for use with aerial lines must be designed to withstand the mechanical loads determined for their operation over the designed operational life of the line.

        (2)         Structures and footings for lines must be designed so as to comply with the listed standards or achieve, to the satisfaction of the Technical Regulator, the same or better safety and technical outcomes.

9—Facade mounted cables

        (1)         Cables and accessories designed for facade mounting must be constructed with suitable insulated conductors and be manufactured to be durable for the environment and service conditions for which they are designed.

        (2)         In determining electrical service conditions and the physical environment under which the line will operate, due care must be given to the consideration of extremes that may occur, the likelihood of their occurrence and the associated risks.

        (3)         Mechanical loading conditions must be determined in accordance with the guidelines set out in the listed standards.

10—Safety clearances

        (1)         Aerial lines must be designed to maintain safety clearances to the ground and other buildings or structures under the environmental and electrical service conditions determined for the line.

        (2)         In determining circuit arrangement, electrical service conditions and the physical environment under which the line will operate, due care must be given to the consideration of extremes that may occur, the likelihood of their occurrence and the associated risks.

        (3)         The environmental and electrical conditions for the determination of clearances to lines must be determined in accordance with the listed standards.

        (4)         Aerial lines must be designed so that safety clearances are as follows:

            (a)         for an aerial line (other than a facade mounted line) constructed to operate at a voltage of 66 kV or less—so that the vertical or horizontal distance from any building or structure (other than a support to which the aerial line is attached or a support of another overhead line which crosses the aerial line) to any position to which a conductor in the aerial line may sag at maximum design temperature, or move as a result of normal prevailing wind pressures, is not less than the relevant distance as set out in Table 1;

Note—

The figures following Table 1 are to be used to assist in understanding the information contained in the Table.

            (b)         for an aerial line (other than a facade mounted line) constructed to operate at a voltage of more than 66 kV—so that the horizontal distance from any building or structure (other than a support to which the aerial line is attached or a support of another overhead line which crosses the aerial line) to the centre-line of the aerial line is not less than the relevant distance as set out in Table 1;

Note—

The figures following Table 1 are to be used to assist in understanding the information contained in the Table.

            (c)         for an aerial line (other than a service line, other cable system or aerial line within a substation)—so that the distance to the ground in any direction from a position to which any part of the aerial line may sag at maximum design temperature, or move as a result of normal prevailing wind pressures, is not less than the relevant distance as set out in Table 2;

            (d)         for a service line or other cable system—so that the distance to the ground in any direction from a position to which any part of the service line or cable system may sag at maximum design temperature, or move as a result of normal prevailing wind pressures, is not less than the relevant distance as set out in Table 3;

            (e)         for a facade mounted line

                  (i)         so that the distance from any part of the facade of the building which supports a line to any position to which the line may sag at maximum design temperature is not less than the relevant distance set out in Table 4;

                  (ii)         where it is designed so the line is more than 0.3 m from the facade of the building supporting it—so that the requirements of paragraphs (a) and (d) are complied with.

        (5)         The arrangement of and clearances between circuits, either attached to a common structure, unattached, in shared spans or crossing, must be designed to be safe for the environmental and electrical service conditions for which they are designed and so as to comply with the listed standards or achieve, to the satisfaction of the Technical Regulator, the same or better safety and technical outcomes.

        (6)         Aerial lines operating at a voltage greater than 66 kV must not be installed above any building or structure.

11—Installation of aerial lines

Aerial lines must be installed in accordance with the guidelines set out in the listed standards.

12—Maintenance of aerial lines

        (1)         Aerial lines, their structures and components must be maintained to be in a safe operating condition.

        (2)         A system of maintenance must be instituted for aerial lines, their structures and their components, including—

            (a)         predetermined processes to confirm the safe state of components;

            (b)         managed replacement programs for components approaching the end of their serviceable life.

        (3)         Maintenance programs must be carried out in accordance with the listed standards.

13—Tables

TABLE 1: Clearance distances between aerial lines (other than facade mounted lines) and buildings or structures

Direction

Distance measured from nearest conductor (in metres)

Distance measured from centre-line of aerial line (in metres)


U ≤ 1 000 V

U > 1 000 V

U > 1 000 V
U ≤ 33 kV

U > 33 kV
U ≤ 66 kV

U > 66 kV
U ≤ 132 kV

U > 132 kV
U ≤ 275 kV

U > 275 kV
U ≤ 330 kV

U > 330 kV
U ≤ 500 kV


Insulated

Bare

Insulated

Bare or covered

Bare

Bare

Bare

Bare

Bare



neutral

active

with earthed screen

without earthed screen



single pole

other




Vertically above those parts of a building or structure normally accessible to persons (A)

2.7

2.7

3.7

2.7

3.7

5.5

6.7

N/A

N/A

N/A

N/A

N/A

Vertically above those parts of a building or structure not normally accessible to persons but on which a person can stand (B)

0.1

2.7

2.7

2.7

2.7

4.7

5.5

N/A

N/A

N/A

N/A

N/A

Horizontally from those parts of a building or structure normally accessible to persons or that is not normally accessible to persons but on which a person can stand (C)

0.1

0.9

1.5

1.5

1.5

3.1

5.5

15.0

20.0

25.0

30.0

38.0

In any direction from those parts of a building or structure not normally accessible to persons (D)

0.1*

0.3*

0.6*

0.1

0.6

2.5

4.5

15.0

20.0

25.0

30.0

38.0

In any direction from ground

Refer to Table 2 or 3

Refer to Table 2

* This clearance can be further reduced to allow for termination at the point of attachment.

Table 1 figures—

        (1)         Figures (a) and (b) will assist in understanding the required minimum safety clearance for aerial lines constructed to operate at a voltage of more than 66 kV.

        (2)         Figure (c) will assist in understanding the required minimum safety clearance for aerial lines constructed to operate at a voltage of 66 kV or less (that is, minimum safety clearance from nearest conductor (maximum swing and sag)).

            (a)        

2012.199.UN19.jpg

            (b)        

2012.199.UN20.jpg

            (c)        

2012.199.UN21.jpg

Vertical dimension (A) applies for example to:
· Balconies
· Terraces
· Walkways
· Bridges
· Scaffolds

Vertical dimension (B) applies in relation to things such as:
· Roofs with a slope of less than 45°
· Parapets wider than 0.1 m
· Pergolas
· Carports

Horizontal dimension (C) applies to the same as (A) and (B)

Horizontal dimension (D) applies in relation to things such as:
· Roofs with a slope of 45° or more
· Poles
· Light Poles

TABLE 2: Clearance distance for aerial lines (excluding service lines, other cable systems and aerial lines within substations)

Nominal System Voltage (U)

Clearance Distance (in metres)


Over carriageway of road

Over land other than carriageway of road

Over land not traversable by vehicles

Bare or insulated conductor
U ≤ 1 kV

5.5

5.5

4.5

Insulated conductor with earthed screen
U > 1 kV

5.5

5.5

4.5

Insulated conductor without earthed screen
U > 1 kV

6.0

5.5

4.5

Bare or covered conductor
1 kV < U ≤ 33 kV
33 kV < U ≤ 132 kV
132 kV < U ≤ 275 kV
275 kV < U ≤ 330 kV
330 kV < U ≤ 500 kV

6.7
6.7
7.5
8.0
9.0

6.0
6.7
7.5
8.0
9.0

4.5
5.5
6.0
6.7
7.5

TABLE 3: Clearance distances for aerial service lines and other cable systems

Location of Line

Clearance Distance (in metres)

Over a road or part of a road specified by the Technical Regulator as being a preferred route for vehicles with loads exceeding the height restrictions under Part 4 of the Road Traffic Act 1961

6.5

Over any part of a main road within the meaning of the Highways Act 1926

5.5

Over the centre of each carriageway of a public road

5.5

Over any other part of a road

4.6

Over any part of a driveway

3.0

Elsewhere

2.7

TABLE 4: Facade mounted lines


Facade Situation

Clearance Distances (in metres)

A

Clearance vertically from ground at footway level

2.5*

B

Above windows and doors

0.3*

C

Each side and below windows

0.5*

D

Each side of doors and balconies

1.0*

E

From metallic parts of buildings, eg downpipes

0.05*

1         This clearance may be reduced based on a proper risk assessment in any case where additional mechanical protection is provided to the cable.

Table 4 figures—

2012.199.UN22.jpg

The following figures will assist in understanding the information in Table 4.

Appendix—Standards, codes, guides and other documents relating to aerial lines

In this Appendix—

            (a)         ENA means Energy Networks Association Limited.


Conductors


Conductor - Bare overhead - Hard - drawn copper        

AS 1746

Conductor - Bare overhead - Aluminium and aluminium alloy        

AS 1531

Conductor - Bare overhead, aluminium and aluminium alloy - Steel reinforced        

AS 3607

Steel conductors and stays - Bare overhead - Galvanised (SC/GZ)        

AS 1222

Steel conductors and stays - Bare overhead - Aluminium clad (SC/AC)        

AS 1222

Galvanised steel wire strand        

AS 2841

Insulated cables


Electric cables - Polymeric insulated - For working voltages up to and including 0.6/1(1.2) kV        

AS/NZS 5000

Electric cables - Polymeric insulated - For distribution and service applications        

AS/NZS 4961

Electric cables - Cross-linked polyethylene insulated - Aerial bundled - For working voltages up to and including 0.6/1(1.2) kV        

AS/NZS 3560

Mechanical fittings for low voltage aerial bundled cable        

AS 3766

Electric cables - Aerial bundled - Polymeric insulated - Voltages 6.35/11(12) kV and 12.7/22(24) kV - Metallic screened        

AS/NZS 3599

Electric cables - Aerial bundled - Polymeric insulated - Voltages 6.35/11(12) kV and 12.7/22(24) kV - Non-metallic screened        

AS/NZS 3599

Conductors - Covered overhead - For working voltages 6.35/11(12) kV up to and including 19/33(36) kV        

AS/NZS 3675

Insulators


Insulators - Ceramic or glass - Station post for indoor and outdoor use - Voltages greater than 1 000 V ac        

AS 4398

Insulators - Porcelain and glass for overhead powerlines - Voltages greater than 1 000 V ac - Test methods - Insulator units        

AS/NZS 2947

Insulators - Porcelain and glass for overhead powerlines - Voltages greater than 1 000 V ac        

AS/NZS 2947

Insulators - Porcelain and glass for overhead powerlines - Voltages greater than 1 000 V ac - Couplings        

AS 2947

Insulators - Porcelain and glass for overhead powerlines - Voltages greater than 1 000 V ac - Test methods - Insulator strings and insulator sets        

AS/NZS 2947

Insulators - Porcelain and glass, pin and shackle type - Voltages not exceeding 1 000 V ac        

AS 3608

Insulators - Porcelain stay type - Voltages greater than 1 000 V ac        

AS 3609

Guidelines for the design and maintenance of overhead distribution and transmission lines—


            (a)         Selection        

ENA C(b)1

Insulator and conductor fittings


Insulator and conductor fittings for overhead powerlines - Performance, material, general requirements and dimensions        

AS 1154

Insulator and conductor fittings for overhead powerlines - Performance and general requirements for helical fittings        

AS 1154

Thermal limits


Guidelines for the design and maintenance of overhead distribution and transmission lines—


            (a)         Thermal limits        

ENA C(b)1

Current rating of bare overhead line conductors        

ENA D(b)5

Short circuit capacity


Guidelines for the design and maintenance of overhead distribution and transmission lines—


            (a)         Fault ratings        

ENA C(b)1

Mechanical loading conditions


Guidelines for the design and maintenance of overhead distribution and transmission lines—


            (a)         Mechanical loading conditions        

ENA C(b)1

Structural design actions - General principles        

AS/NZS 1170

Structural design actions - Permanent, imposed and other actions        

AS/NZS 1170

Structural design actions - Wind actions        

AS/NZS 1170

Minimum design loads on structures (known as the SAA Loading Code) - Earthquake loads        

AS 1170

Conductor tensions


Guidelines for the design and maintenance of overhead distribution and transmission lines—


            (a)         General        

ENA C(b)1

            (b)         Calculations        

ENA C(b)1

Structures and footings


Guidelines for the design and maintenance of overhead distribution and transmission lines—


            (a)         General        

ENA C(b)1

Methods of testing soils for engineering purposes        

AS 1289

Piling - Design and installation        

AS 2159

Design of steel lattice towers and masts        

AS 3995

Steel structures        

AS 4100

Concrete structures        

AS 3600

Clearances from ground


Guidelines for the design and maintenance of overhead distribution and transmission lines—


            (a)         Environmental and loading conditions        

ENA C(b)1

Clearances from structures


Guidelines for the design and maintenance of overhead distribution and transmission lines—


            (a)         Environmental and loading conditions        

ENA C(b)1

Spacing of conductors


Guidelines for the design and maintenance of overhead distribution and transmission lines—


            (a)         Clearances        

ENA C(b)1

            (b)         Environmental and loading conditions        

ENA C(b)1

Maintenance


Guidelines for the design and maintenance of overhead distribution and transmission lines—


            (a)         Maintenance and inspection procedures        

ENA C(b)1



AustLII: Copyright Policy | Disclaimers | Privacy Policy | Feedback