BUILDING REGULATIONS 2018 - SCHEDULE 8

Schedule 8—Essential safety measures

Regulation 214

Part 1—Building fire integrity

Column 1

Item

Column 2

Safety measure

1

Building elements required to satisfy prescribed fire-resistance levels

2

Materials and assemblies required to have fire hazard properties

3

Elements required to be non-combustible, provide fire protection, compartmentation or separation

4

Wall-wetting sprinklers (including doors and windows required in conjunction with wall-wetting sprinklers)

5

Fire doors (including sliding fire doors and their associated warning systems) and associated self‑closing, automatic closing and latching mechanisms

6

Fire windows (including windows that are automatic or permanently fixed in the closed position)

7

Fire shutters

8

Solid core doors and associated self-closing, automatic closing and latching mechanisms

9

Fire-protection at service penetrations through elements required to be fire-resisting with respect to integrity or insulation, or to have a resistance to the incipient spread of fire

10

Fire protection associated with construction joints, spaces and the like in and between building elements required to be fire-resisting with respect to integrity and insulation

11

Smoke doors and associated self-closing, automatic closing and latching mechanisms

12

Proscenium walls (including proscenium curtains)

Part 2—Means of egress

Column 1

Item

Column 2

Safety measure

1

Paths of travel to exits

2

Discharge from exits (including paths of travel from open spaces to the public roads to which they are connected)

3

Exits (including fire-isolated stairways and ramps, non fire-isolated stairways and ramps, stair treads, balustrades and handrails associated with exits, and fire-isolated passageways)

4

Smoke lobbies to fire-isolated exits

5

Open access ramps or balconies for fire-isolated exits

6

Doors (other than fire or smoke doors) in a required exit, forming part of a required exit or in a path of travel to a required exit, and associated self-closing, automatic closing and latching mechanisms

Part 3—Signs

Column 1

Item

Column 2

Safety measure

1

Exit signs (including direction signs)

2

Signs warning against the use of lifts in the event of fire

3

Warning signs on sliding fire doors and doors to non-required stairways, ramps and escalators

4

Signs, intercommunication systems, or alarm systems on doors of fire-isolated exits stating that re-entry to a storey is available

5

Signs alerting persons that the operation of doors must not be impaired

6

Signs required on doors, in alpine areas, alerting people that they open inwards

7

Fire order notices required in alpine areas

Part 4—Lighting

Column 1

Item

Column 2

Safety measure

1

Emergency Lighting

Part 5—Fire fighting services and equipment

Column 1

Item

Column 2

Safety measure

1

Fire hydrant system (including on-site pump set and fire-service booster connection)

2

Fire hose reel system

3

Sprinkler system

4

Portable fire extinguishers

5

Fire control centres (or rooms)

Part 6—Air-handling systems

Column 1

Item

Column 2

Safety measure

1

Smoke hazard management systems—

(a)     automatic air pressurisation systems for fire‑isolated exits;

(b)     zone smoke control system;

(c)     automatic smoke exhaust system;

(d)     automatic smoke-and-heat vents (including automatic vents for atriums);

(e)     air-handling systems that do not form part of a smoke hazard management system and which may unduly contribute to the spread of smoke;










(f)     miscellaneous air-handling systems serving more than one fire compartment to which Sections 5 and 6 of AS/NZS 1668.1 The use of ventilation and air conditioning in buildings—Part 1: Fire and smoke control in buildings, as in force or as re-issued or as published from time to time;

(g)     other air-handling systems.

2

Car park mechanical ventilation system

3

Atrium smoke control system (see item 1(d) for smoke and heat vents)

Part 7—Automatic fire detection and alarm systems

Column 1

Item

Column 2

Safety measure

1

Smoke and heat alarm system

2

Smoke and heat detection system

3

Atrium fire detection and alarm system

Part 8—Occupant warning systems

Column 1

Item

Column 2

Safety measure

1

Sound system and intercom system for emergency purposes

2

Building occupant warning system

Part 9—Lifts

Column 1

Item

Column 2

Safety measure

1

Stretcher facilities in lifts

2

Emergency lifts

3

Passenger lift fire service controls

Part 10—Standby power supply system

Column 1

Item

Column 2

Safety measure

1

Standby power supply system

Part 11—Building clearance and fire appliances

Column 1

Item

Column 2

Safety measure

1

Open space around large isolated buildings

2

Vehicular access around large isolated buildings

Part 12—Mechanical ventilation and hot, warm and cooling water systems

Column 1

Item

Column 2

Safety measure

1

Mechanical ventilation systems incorporating cooling tower systems (other than a system serving only a single sole-occupancy unit in a Class 2 or 3 building or a Class 4 part of a building)

2

Mechanical ventilation systems incorporating hot and warm water systems (other than a system serving only a single sole-occupancy unit in a Class 2 or 3 building or a Class 4 part of a building)