ELECTRICITY SAFETY (INSTALLATIONS) REGULATIONS 2009 (SR NO 164 OF 2009) - REG 238

Prescribed electrical installation work

    (1)     For the purposes of section 45 of the Act, prescribed electrical installation work means work on all or part of any of the following electrical installations if they are ordinarily operated at low voltage or a voltage exceeding low voltage—

        (a)     consumer's mains, main earthing systems, consumer's terminals connection devices, any supports for overhead service lines (including any poles) and those parts of main switchboards that are related to the control of installations and the protection against the spread of fire;

        (b)     if a main switchboard or a replacement main switchboard is connected for the first time, any circuit protective devices, switchgear, controlgear, circuit breakers and wiring systems of that main switchboard in place at the time that the items set out in paragraph (a) are inspected;

        (c)     sub-mains, earthing systems and any distribution boards related to the control of individual occupiers' portions of multiple installations;

        (d)     if a distribution board related to the control of individual occupiers' portion of a multiple installation, or a replacement distribution board related to the control of individual occupiers' portion of a multiple installation, is connected for the first time, any circuit protective devices, switchgear, controlgear, circuit breakers and wiring systems of that distribution board in place at the time the items set out in paragraph (c) are inspected;

        (e)     high voltage installations, except high voltage electrical equipment that is—

              (i)     associated with an electric discharge lighting system; or

              (ii)     associated with X-ray equipment; or

              (iii)     associated with high frequency equipment; or

              (iv)     within self contained equipment supplied at low voltage;

        (f)     wiring systems, switchgear, controlgear and accessories installed to provide control and protection of generation systems (excluding stand-alone power systems with a power rating that is less than 500 volt-amperes);

        (g)     electric fences used for security purposes but not including electric fences intended primarily for the containment of animals;
r. 238

        (h)     electrical equipment installed in a hazardous area and electrical equipment associated with the protection of a hazardous area but not installed within the hazardous area;

              (i)     circuit protective devices, switchgear, controlgear, wiring systems and accessories (other than fire detection and alarm systems) installed to provide control and protection of passenger lifts, fire pumps (excluding pumps for fire hose reels where those hose reels are not the sole means of fire protection) and air handling systems intended to exhaust and control the spread of fire and smoke;

        (j)     a part 1 solution installed in an electrical installation.

    (2)     For the purposes of section 45 of the Act, prescribed electrical installation work means work on all or part of any fixed electrical equipment operated at any voltage installed in a patient area.

    (3)     For the purposes of section 45 of the Act, prescribed electrical installation work does not include—

        (a)     the repair or maintenance of a single component part of an electrical installation; or

        (b)     the replacement of a single component part of an electrical installation by an equivalent component part at the same location.

    (4)     A single component referred to in subregulation (3) includes any terminating device required to connect that single part of an electrical installation to the electricity supply.