A person must not—
(a) place or allow to remain any flammable material closer than 3000 millimetres in any direction from a wall or fence of any substation or switch yard that forms part of a relevant installation; or
(b) place or allow to remain any flammable material vertically below an aerial line that forms part of a relevant installation; or
(c) place or allow to remain any flammable material so that, at any time, the flammable material is closer than the relevant horizontal distance specified in Row A of Table 314 from any point of the vertical projection below an aerial line that forms part of a relevant installation; or
(d) place or allow to remain any material so that, at any time, the material is closer than the relevant horizontal distance marked "h" specified in Row B of Table 314 from any point of the vertical projection below an aerial line that forms part of a relevant installation unless the material is no closer vertically below the line than the vertical distance marked "v" specified in Row B of Table 314.
Penalty: 20 penalty units.
TABLE 314—Minimum distances from materials to aerial lines