Victorian Numbered Regulations

[Index] [Table] [Search] [Search this Regulation] [Notes] [Noteup] [Previous] [Next] [Download] [Help]

ELECTRICITY SAFETY (INSTALLATIONS) REGULATIONS 2009 (SR NO 164 OF 2009) - REG 319

Tree clearing

    (1)     A person, other than an authorised person, must not prune or clear the whole or any part of a tree if the tree or any part of the tree that is pruned or cleared could fall closer to a relevant installation than—

        (a)     in the case of a relevant installation operating at low voltage, 2 metres in all directions; and

        (b)     in the case of a high voltage electrical installation or aerial line of a small gauge railway with a voltage set out in Row A in Column 1 or 2 of Table 319, the relevant minimum distance specified in Row B in Column 1 or 2 of Table 319.

Penalty:     20 penalty units.

    (2)     An authorised person must, before pruning or clearing the whole or any part of a tree to which subregulation (1) applies, notify the owner of the relevant installation.

Penalty:     20 penalty units.

    (3)     In this regulation authorised person means a person who holds a current certificate specifying satisfactory completion of a training course in tree clearing, approved by Energy Safe Victoria.

TABLE 319—Minimum distances from falling trees or parts of trees to high voltage electrical installations and aerial lines of a small gauge railway or tramway system



Column 1

Column 2



Nominal voltage ("U")

A


U ≤ 66kV
alternating current
or
U ≤1500V d.c. traction conductor

U > 66kV alternating current or
U > 1500V direct current

B

Minimum distance in all directions

2000 mm

6000 mm



AustLII: Copyright Policy | Disclaimers | Privacy Policy | Feedback