(1) Subject to this
regulation, emergency lighting shall be provided in a public building in
accordance with Building Regulations and AS/NZS 2293.
(2) An emergency
lighting system shall be maintained in accordance with AS/NZS 2293.
(3) Where an emergency
lighting system operates through contactors or is remotely operated through a
control system, provisions which are “fail safe” shall be made to
automatically provide energy for the emergency luminaires in the event of a
fault that extinguishes the general lighting required to be provided under
these regulations.