Provision
|
Modification
|
Clause B2D5
|
After “fixture” insert:
for a new heated water installation, or for an existing heated water
installation if the requirements in this clause applied to the installation
when it was a new installation,
|
|
Before the Application statement insert:
The delivery temperature of heated water at the outlet of each sanitary
fixture (other than a basin in a Class 1, 2, 4, 5, 6, 7, 8 or 10
building) for an existing heated water installation must meet the requirements
for a new heated water installation if —
(a) in relation to a heated water installation
with multiple water heaters — all water heaters in the installation
are replaced or relocated; or
(b) in any other case — a water heater
in the installation is replaced or relocated or an additional water heater is
added to the installation.
|
|
Delete the Application statement and insert:
B2D5 applies to heated water installations intended for personal hygiene as
stated in the clause.
|
Clause B2D6
|
Delete the Application statement and insert:
B2D6 applies to heated water installations to which B2D5 applies.
|
Provision
|
Modification
|
Clause 2.3
|
Delete paragraph (a) and insert:
(a) Bends in pipes shall —
(i)
have a throat radius complying with AS/NZS 1260:2017
(PVC‑U pipes and fittings for drain, waste and vent applications)
Table 5.6 and Figure B6; and
(ii)
be free from wrinkling and flattening.
|
Clause 3.8.2
|
Delete paragraph (b) and insert:
(b) the drains laid through footings shall be
installed with an annular space of not less than 25 mm filled with a
liner of flexible material. However, the drains need not be installed in such
a way if the drains are installed in a building that is —
(i)
classified as a Class 1a or 10a building under
Volume 1 and 2 of the National Construction Code; and
(ii)
in sandy soil classified as Class ‘A’ within
the meaning of AS 2870‑2011 (Residential slabs and footings).
|
Clause 3.18
|
Delete paragraph (d) and insert:
|
|
(d) A vacuum sewer system DN 100 downstream
vent shall be connected on the main drain —
(i)
before or on the inspection shaft riser; and
(ii)
after the last fixture on the main drain.
The vacuum sewer system DN 100 downstream
vent should be connected as close as possible to the inspection shaft riser.
|
|
(e) Vacuum sewer system and boundary trap low
level vents shall terminate between a minimum of 150 mm and a maximum of
250 mm above ground or adopted flood level using one of the following
methods —
|
|
(i)
one 88° bend and a flat grate with invert level not
less than 150 mm above ground or adopted flood level;
|
|
(ii)
two 88° bends and a flat grate or vent cowl so that
there is not less than 150 mm between the flat grate or vent cowl and the
ground or adopted flood level;
|
|
(iii)
an air admittance valve not less than 150 mm above
ground or adopted flood level installed in accordance with Clause 6.9.
|
Clause 4.5.3
|
Delete paragraph (b).
At the end of the clause insert:
However, if the reflux valve is being installed in relation to an existing
building, the reflux valve may be installed upstream from the inspection
shaft.
|
Clause 4.6.2
|
Delete paragraph (b) and insert:
(b) have each gully riser provided with a grating
or cover of a loose, pop‑out type to relieve surcharge and allow
adequate ventilation to the gully riser; and
|
|
In paragraph (c)(ii) delete “surround).” and insert:
surround); and
|
|
At the end of the clause insert:
(d) in relation to a class 1a or class 10a
building within the meaning of Volume 1 and 2 of the National
Construction Code — have the height of the gully riser not more
than 600 mm measured from the top of the water seal to the grate of the
gully.
|
Table 4.6.6.6
|
Delete the table and insert:
TABLE 4.6.6.6
POINT OF MEASUREMENT ON FIXTURES FOR HEIGHT ABOVE OVERFLOW GULLY
Fixture
Point of measurement
Floor waste gully
Top surface level of the grate
All other fixtures (including greywater diversion devices)
Overflow level of the fixture
|
Clause 4.7.1
|
Delete paragraph (c) and insert:
(c) on the downstream end of any branch drain that
exits a building, between the building and the junction into the main drain;
|
Clause 6.5.1
|
Delete the clause and insert:
6.5.1 General
Each sanitary fixture and appliance must have a self‑sealing device or
trap.
A self‑sealing device must —
(a) be in the same room as the fixture or
appliance that it serves; and
(b) be accessible.
A trap (other than a self‑sealing device) must —
(a) be in the same room as the fixture or
appliance that it serves; and
(b) be accessible unless the trap is in the ground
or concrete.
A trap (other than a self‑sealing device) in the ground or concrete must
not have —
(a) a loose coupling nut; or
(b) a diameter that is greater than the diameter
of the outlet for the fixture or appliance that the trap serves.
A trap (other than a self‑sealing device) that is in the ground or
concrete must be directly below the outlet for the fixture or appliance that
the trap serves.
|
Clause 13.9
|
Delete the passage that begins with “Where” and continues to the
end of the clause.
|