Western Australian Repealed Regulations

[Index] [Table] [Search] [Search this Regulation] [Notes] [Noteup] [Previous] [Next] [Download] [Help]

This legislation has been repealed.

GAS STANDARDS (GASFITTING AND CONSUMERS' GAS INSTALLATIONS) REGULATIONS 1999 - SCHEDULE 6

[r. 32(1)(a)]

Division 1 — Interpretation

101 .         Definitions

                In this Schedule, unless the contrary intention appears —

        “approved” means approved by —

            (a)         the Director; or

            (b)         a person recognized by the Director as a competent authority for that purpose;

        “bedroom” means any room used or intended to be used as sleeping quarters;

        “flame safeguard system” means a system designed to detect flame failure and shut off the flow of gas when flame failure is detected;

        “prescribed pressure” means —

            (a)         0.75 kPa, , in relation to a gas installation that uses or is to use tempered LPG (i.e. a mixture of LPG and air having a gross heating value of more than 23.5 MJ/m 3 but not more than 27.3 MJ/m 3 );

            (b)         1.25 kPa, in relation to a gas installation that uses or is to use natural gas or simulated natural gas (i.e. a mixture of LPG and air having a gross heating value of more than 40 MJ/m 3 but not more than 51 MJ/m 3 );

            (c)         2.75 kPa, in relation to a gas installation that uses or is to use LPG.

Division 2 Master meters

201 .         Application

                This Division applies in addition to clause 4.14 of AG 601 — 1998.

202 .         Location of master meters

                A master meter must be installed in a location approved by the gas supplier and must not be moved without the approval of the gas supplier.

203 .         Position of master meters generally

                A master meter must be installed so that —

            (a)         it is at all times clear of the ground and in a level position; and

            (b)         it is at all times readily accessible for reading, servicing, adjustment or replacement.

204 .         Prohibited positions

                A master meter must not be installed —

            (a)         in a bedroom;

            (b)         in a position in which it is inadequately ventilated;

            (c)         in such a position that it will be subjected to wide variations of temperature or to other conditions that are likely to affect its accuracy;

            (d)         closer than one metre to any appliance combustion air inlet;

            (e)         in a room primarily for housing electrical meters or switchgear;

            (f)         closer than one metre to electrical equipment capable of providing a source of ignition of the gas metered or to an electric meter, unless the gas meter and the electrical equipment or electric meter, as the case may be, are installed in separate and adequately ventilated housings each of which is sealed from the other; or

            (g)         beneath a liquid fuel storage tank, or closer than 500 mm measured laterally to any such tank.

205 .         Master meter boxes

                A master meter, and any associated regulator, must be installed —

            (a)         in a meter box or housing that has a supporting base and is provided specifically for that purpose; or

            (b)         otherwise to the satisfaction of the gas supplier.

206 .         Master meter boxes in cavity walls

                If a master meter is installed in a cavity wall, the meter box or housing containing the meter must be completely sealed with fireproof materials from any adjoining recess or cavity and must be ventilated to the outside atmosphere.

207 .         Prepayment meters

                The outlet of a prepayment meter to which more than one appliance is connected must be fitted with —

            (a)         an approved valve designed to automatically shut off the flow of gas when an unsafe condition is detected; and

            (b)         an approved manual reset system,

                unless every appliance connected to the prepayment meter is fitted with an approved flame safeguard system.

208 .         Identification of master meters

                A master meter must be clearly identifiable with the consumer’s gas installation to which it measures the supply of gas.

Division 3 — LPG cylinders and tanks

301 .         Location of cylinders, tanks and regulators

        (1)         The location of cylinders, tanks and regulators must comply with AS/NZS 1596: 1997.

        (2)         This clause applies in addition to clause 6.3.1 of AG 601 — 1998.

302 .         Housings

        (1)         Equipment other than a cylinder and its essential fittings must not be stored, placed, or allowed to remain, within a housing specifically provided for a cylinder.

        (2)         This clause applies in addition to clause 6.3.10 of AG 601 — 1998.

303 .         Pressure relief valve outlets

        (1)         The pressure relief valve outlet of a cylinder or tank must be positioned so that any gas discharged through the valve would be directed away from any building, structure, caravan, towing vehicle, marine craft or gas installation.

        (2)         A pressure relief valve outlet must not be located in any building, structure, caravan, or marine craft (except as permitted by clause 301) unless it is located within a housing specifically provided for that purpose.

        (3)         This clause applies in place of clause 6.4 of AG 601 — 1998.

304 .         Appliances not to be connected to gas supply for mobile engines

                An appliance other than a mobile engine must not be connected to a storage container that provides the supply of gas to a mobile engine.

Division 4 Fitting lines and fittings

401 .         Fitting lines and fittings

        (1)         A fitting line or fitting on a consumer’s gas installation that is to operate at a pressure of 200 kPa or less must comply with AG 601 — 1998.

        (2)         A fitting line or fitting on a consumer’s gas installation that is to operate at a pressure exceeding 200 kPa must comply with AS 4041 — 1992.

402 .         PVC fitting lines

        (1)         A PVC fitting line may only be used in such a position as to be readily accessible for the purposes of any repairs and maintenance that become necessary.

        (2)         This clause applies in addition to Table 3.1 of AG 601 — 1998.

403 .         Outlet not in use to be sealed

                An outlet provided for the connection of an appliance must be sealed gas-tight in an approved manner or with an approved fitting when an appliance is not connected to it or is not about to be connected to it.

404 .         Ventilating or air ducts

        (1)         A fitting line must not be installed in or through any ventilating or other air duct.

        (2)         This clause applies —

            (a)         in addition to clause 4.11.1 of AG 601 — 1998; and

            (b)         in place of clause 4.11.17 of AG 601 — 1998.

405 .         Pressure holding capability of consumer’s gas installations

                A consumer’s gas installation must not leak when subjected to an approved test.

406 .         Protection from excessive pressure

        (1)         If the inlet pressure to a fitting line regulator exceeds 7 kPa, an over-pressure protection device must be incorporated in the regulator or installed in the fitting line before the regulator to prevent the pressure at the outlet of the regulator at any time exceeding the maximum pressure for which any fitting line or gas fitting supplied through the regulator has been found upon test to be suitable.

        (2)         In subclause (1) —

        “fitting line regulatormeans a regulator installed in a fitting line, other than a regulator that controls the gas pressure to one appliance only, whether or not it is an integral part of the appliance.

        (3)         This clause applies in place of clause 4.6 of AG 601 — 1998.

Division 5 Appliances generally

501 .         Approval of appliances

        (1)         A Type A appliance must not be installed in a consumer’s gas installation unless —

            (a)         it is the same as an appliance that is currently approved for such installation by the Director; or

            (b)         it is individually approved for such installation by an inspector,

                and is marked with a badge or label to this effect.

        (2)         A Type B appliance must not be installed in a consumer’s gas installation unless —

            (a)         it is the same as an appliance that is currently approved for such installation by the Director; or

            (b)         it is individually approved in writing for such installation by an inspector.

502 .         Type of gas

        (1)         An appliance installed in a consumer’s gas installation must not be connected to a cylinder or reticulated supply system from which the gas supplied or to be supplied is not of a type approved for use by that appliance.

        (2)         An appliance installed in a consumer’s gas installation must not be modified after manufacture for the purpose of enabling it to use gas of a different type unless it is modified —

            (a)         in accordance with the manufacturer’s instructions using a conversion kit specifically approved for that purpose; or

            (b)         with the written approval of an inspector.

503 .         Avoidance of hazards

        (1)         An appliance, cylinder, flue, fitting line or other apparatus must not, by its construction, use or positioning, constitute a hazard.

        (2)         Nothing in this Schedule limits the generality of subclause (1).

504 .         Restrictions as to certain rooms

        (1)         There must not be installed in any bedroom, bathroom, toilet, shower room, shower cubicle or sauna —

            (a)         any appliance that is not fitted with a flue; or

            (b)         the outlet plug of any bayonet fitting for a portable appliance.

        (2)         The outlet plug of a bayonet fitting can be installed in a room to which subclause (1) does not apply only if —

            (a)         the room is used as a kitchen; or

            (b)         the room has a volume of more than 30 cubic metres, and 2 permanent ventilation openings —

                  (i)         one of which is situated near the top of the room and the other near the bottom of the room;

                  (ii)         that are separated by a distance of not less than 1.5 metres measured vertically; and

                  (iii)         each of which has an aggregate open area of not less than 25 000 mm²;

                or

            (c)         the installation is approved in each case by an inspector.

        (3)         An appliance must not be installed or connected for use in a sauna unless the approval of an inspector has been given to such installation or use of that particular appliance.

        (4)         In this clause —

        “bathroom” means a bathroom in a private residence and does not include an ablution area serving a factory or a camping area, or any other ablution area serving a communal purpose;

        “bayonet fittingmeans a bayonet-style outlet plug and a mating socket such that gas is not able to pass from the outlet plug until the plug is inserted in, and locked into, the mating socket.

505 .         Safety devices

                An appliance that is supplied or to be supplied from a reticulated supply system and is designed to use air, oxygen, or any other gas under pressure together with the gas from the supply system must be fitted with such safety devices, if any, as the gas supplier is satisfied will prevent the entry into the supply system of air, oxygen, or such other gas, as the case may be.

506 .         Flues

        (1)         Unless otherwise permitted by these regulations, the product of combustion from an appliance must be discharged to the outside atmosphere by means of a flue fitted to the appliance that complies with this clause.

        (2)         A flue must be constructed of material that is —

            (a)         mechanically robust;

            (b)         resistant to internal and external corrosion;

            (c)         durable; and

            (d)         non-combustible.

        (3)         In the case of a natural draught flue, the flue must be fitted with a flue cowl (i.e. a fitting placed at a flue terminal to ensure the proper discharge of flue gas) of an approved type unless the flue terminal is permitted by these regulations to be between the ceiling and the roof of a building.

        (4)         If flue gases from 2 or more flue pipes are or may be discharged into a common flue, the flue must be constructed to the satisfaction of an inspector.

        (5)         A flue terminal must not be located closer than one metre to —

            (a)         a gas meter;

            (b)         a liquid fuel or flammable liquid storage tank; or

            (c)         an LPG cylinder.

        (6)         A flue must not be fitted to an appliance installed in a consumer’s gas installation if the flue has been used as a flue on any other appliance or device that was not using fuel of the same kind.

        (7)         Subclause (6) does not apply to a flue that is clear of obstructions and otherwise complies with the requirements of these regulations for flues.

        (8)         This clause applies in addition to clause 5.13 and Appendix H of AG 601 — 1998.

507 .         Hoods or canopies

        (1)         If the use of a hood or canopy to discharge flue products to the outside atmosphere has been approved as part of an appliance approval, the hood or canopy —

            (a)         must have an opening that is not less than 4 times the area encompassed by the outer perimeter of the flue;

            (b)         must be positioned vertically above the centre of the appliance exhaust outlet opening; and

            (c)         must be positioned so that the lowest part is not more than 200 mm from the appliance exhaust outlet opening.

        (2)         This clause applies in addition to clauses 5.12.17 and 5.13.9 of AG 601 — 1998.

508 .         Electrical

        (1)         An appliance that is installed in a consumer’s gas installation and incorporates electrical apparatus must comply with AS 3100 — 1997.

        (2)         An appliance installed in a consumer’s gas installation and connected to a supply of electricity must be provided with a means of isolation from the electricity supply that —

            (a)         does not need tools to effect the isolation; and

            (b)         is located adjacent to the appliance and in a readily accessible position.

Division 6 — Additional requirements for particular appliances

601 .         Cooking appliances

        (1)         A cooking appliance installed in a consumer’s gas installation must not be so located that any combustible material would be likely to be affected by heat from a burner of the appliance.

        (2)         A fryer installed in a consumer’s gas installation must not be located —

            (a)         within 500 mm of a barbecue griller, unless a baffle plate extending at least 500 mm above the hob of the fryer is provided between the fryer and the barbecue griller; or

            (b)         within 200 mm of a smooth plate, a griller other than a barbecue griller, or any other appliance that operates so as to expose any open flame or other source of ignition, unless a baffle plate extending to at least 200 mm above the hob of the fryer is provided between the fryer and the other appliance.

        (3)         A cooking appliance installed in a consumer’s gas installation not being a mobile installation must be so installed that any cooking surface or oven rack of the appliance is at all times maintained in a horizontal plane.

        (4)         The oven of a cooking appliance installed in a consumer’s gas installation must be fitted with an approved flame safeguard system.

        (5)         This clause applies in addition to clause 5.12.4 of AG 601 — 1998.

602 .         Water heating appliances

        (1)         Unless otherwise approved, if a gas water heater that does not have a storage facility for heated water is fixed to a wall in which there is any combustible material, the heater must be mounted on —

            (a)         suitable fire resistant material that extends at least 150 mm beyond the projection onto the wall of the heater; or

            (b)         spacers such that there is an air space of not less than 25 mm between the case of the heater and any combustible material.

        (2)         The water outlet of a gas sink heater must not be fitted with any device that restricts the flow of water unless the appliance as manufactured and approved is fitted with such a device.

        (3)         A gas water heater that is mounted externally to any building or other structure must be so located that the heater —

            (a)         is sufficiently clear of trees, shrubs, and other combustible material so as not to constitute a fire hazard; and

            (b)         has sufficient clearance for the necessary plumbing connections.

        (4)         This clause applies in addition to clauses 5.12.5.2 and 5.12.6 of AG 601 — 1998.

603 .         Space heating appliances

        (1)         A gas space heating appliance that is not fitted with a flue must not be installed in a private dwelling unless the appliance is fitted with an approved carbon dioxide sensing device.

        (2)         If the room or space in which there is installed —

            (a)         an appliance referred to in subclause (1); or

            (b)         a bayonet point enabling the connection of such an appliance,

                is ventilated to another room or space, that other room or space and any further room or space to which it is in turn ventilated is to be subject to the ventilation requirements of these regulations as if it were part of the room or space in which the appliance or bayonet point is installed.

        (3)         A gas space heating appliance that heats wholly or partly by means of high temperature radiants or surfaces and that is not fitted with a flue must not be installed in a consumer’s gas installation so as to be located closer to any combustible material than 500 mm measured laterally.

        (4)         This clause applies in addition to clause 5.12.8 and Appendix L of AG 601 — 1998.

604 .         Swimming pool heaters

        (1)         A gas swimming pool heater must be fitted with a device to ensure that water is flowing through the heater before the main gas valve permits the flow of gas to the burners of the heater.

        (2)         This clause applies in addition to clause 5.12.7 of AG 601 — 1998.

Division 7 Caravans

701 .         Application

        (1)         This Division applies to a consumer’s gas installation that is on or in a caravan but not to any other consumer’s gas installation.

        (2)         This Division applies in addition to clause 6.6 of AG 601 — 1998.

702 .         Cylinders and associated equipment

                If a gas cylinder, its valve and regulating equipment, or any part of a consumer’s gas installation between the cylinder and the outlet of the primary pressure regulator is mounted in a compartment or recess, the compartment or recess must be —

            (a)         lined with a fire resistant material; and

            (b)         not accessible from the inside of the caravan.

703 .         Location of appliances

        (1)         An appliance in a caravan must be so located that in the event of a fire, the appliance would not obstruct the exit of a person from any part of the caravan.

        (2)         If an appliance that requires gas to be supplied to it at more than the prescribed pressure is installed in a caravan in accordance with clause 704, the appliance must not be located in a cupboard or other enclosed compartment.

        (3)         Equipment and appliances operating at above prescribed pressure must not be permanently installed in a caravan unless specifically approved.

        (4)         A portable gas appliance in a caravan must be securely packed or fixed by temporary fastenings at all times that the caravan is in motion.

704 .         Pressure

        (1)         The pressure to an appliance installed in a caravan and in a fitting line after the pressure regulator must not exceed the prescribed pressure.

        (2)         Subclause (1) does not apply in respect of —

            (a)         a portable appliance that incorporates its own cylinder the installation of which is in accordance with clause 702; or

            (b)         an appliance that depends on a pressure exceeding the prescribed pressure for its proper operation, if —

                  (i)         the appliance is installed in a mobile workshop that is not used for accommodation; and

                  (ii)         the pressure is limited by a regulator mounted outside the caravan to not more than the minimum pressure required by the appliance for its proper operation, being a pressure of not more than 140 kPa.

        (3)         If in accordance with subclause (2) gas is used at a pressure exceeding the prescribed pressure it must be carried in the vapour phase.

705 .         Warnings

        (1)         The notice referred to in clause 6.6.8.3 of AG 601 — 1998 must be —

            (a)         legible and clear;

            (b)         in a permanent form measuring not less than 200 mm by 200 mm; and

            (c)         kept in a conspicuous position adjacent to an appliance, or if there is more than one appliance, adjacent to one of the appliances.

        (2)         There must be kept in a conspicuous position adjacent to the fuel tank filler of a self-propelled caravan in which there is installed any appliance, a legible and clear warning in a permanent form setting out the following —


DANGER
Ensure all gas appliances are turned off before refuelling.

Division 8 — Marine craft

801 .         Application

        (1)         This Division applies to a consumer’s gas installation that uses or is to use LPG and that is on or in a marine craft but not to any other consumer’s gas installation.

        (2)         This Division applies in addition to clause 6.7 and Appendix K of AG 601 — 1998.

802 .         Accessibility

                A cylinder, regulator, or fitting line that is part of a consumer’s gas installation and all safety equipment pertaining to the consumer’s gas installation must be so located that access to the cylinder and the cylinder valves is readily available and operation of the valves is not obstructed or hindered.

803 .         Cylinders and associated equipment

        (1)         For the purposes of clause 6.7.3.3 of AG 601 — 1998, a cylinder compartment drain —

            (a)         must be connected directly to the outside of the marine craft; and

            (b)         must terminate above the water line.

        (2)         A consumer’s gas installation must be so designed that in order to disconnect the cylinder from the consumer’s gas installation it is necessary to undo only the cylinder valve union.

        (3)         This clause applies both to —

            (a)         a cylinder that is not connected to an appliance; and

            (b)         a cylinder that is connected to an appliance.

804 .         Restricted spaces

        (1)         An appliance, fitting line, or other part of a consumer’s gas installation must not be installed in any space that is not ventilated or that contains explosives, or highly-combustible material.

        (2)         A fitting line must not be installed in any area intended primarily for sleeping.

805 .         Fitting lines

                A fitting line must be located outside any false bottom in a position that is protected and ventilated, is sufficiently elevated to be free from the effects of bilge water, and is not within 50 mm of any electrical cable or electrical fitting.

806 .         Location of appliances

        (1)         An appliance installed in a marine craft must be so located that in the event of a fire, the appliance would not obstruct the exit of a person from any part of the marine craft.

        (2)         If an appliance that requires gas to be supplied to it at more than the prescribed pressure is installed in a marine craft in accordance with clause 807, the appliance must not be located in a cupboard or other enclosed compartment.

        (3)         Equipment and appliances operating at above prescribed pressure must not be permanently installed in a marine craft unless specifically approved.

        (4)         An appliance must be so located that it is not likely to be exposed to air turbulence that would extinguish the flame.

        (5)         An appliance must not be installed below the level of the main deck unless an approved device designed to detect the presence of flammable gas is installed.

        (6)         The device for detecting flammable gas referred to in subclause (5) must be in operation —

            (a)         before any appliance is lit;

            (b)         while the marine craft is being refuelled; and

            (c)         while the marine craft is in use.

807 .         Pressure

        (1)         The pressure to an appliance installed in a marine craft and in a fitting line after the pressure regulator must not exceed the prescribed pressure.

        (2)         Subclause (1) does not apply in respect of —

            (a)         a portable appliance that incorporates its own cylinder the installation of which is in accordance with clause 803(2); or

            (b)         an appliance that depends on a pressure exceeding the prescribed pressure for its proper operation, if —

                  (i)         the appliance is installed in a mobile workshop that is not used for accommodation; and

                  (ii)         the pressure is limited by a regulator mounted outside the marine craft to not more than the minimum pressure required by the appliance for its proper operation, being a pressure of not more than 140 kPa.

        (3)         If in accordance with subclause (2) gas is carried at a pressure exceeding the prescribed pressure it must be carried in the vapour phase.

808 .         Ventilation

        (1)         If natural ventilation is not sufficient to provide for fresh air requirements and to adequately remove any leaked gas from an appliance, the natural ventilation must be supplemented by mechanical means.

        (2)         If mechanical ventilation is provided in a space of which any cylinder or appliance is installed —

            (a)         the fan must be so designed and of such material as to eliminate the risk of sparks being caused by friction or impact of the impeller against the casing;

            (b)         any electric motor driving a fan must be located —

                  (i)         outside the space ventilated;

                  (ii)         within the space ventilated but clear of the ventilation trunking and outlets; or

                  (iii)         in such other position as is approved in each case by an inspector;

            (c)         ventilation outlets are to be so located as to discharge into a place that is free from any source of ignition; and

            (d)         exhaust ventilation trunking must extend to a position near to the bottom of the space and adjacent to any appliance by reason of which mechanical ventilation is required.

809 .         Flues

        (1)         When an appliance is required by these regulations to be fitted with a flue, the flue must be of double-seamed copper or stainless steel having a thickness of —

            (a)         in the case of copper, not less than 0.6 mm; or

            (b)         in the case of stainless steel, not less than 0.45 mm.

        (2)         A flue fitted to an appliance must be fitted with a protective sleeve of 6 mm of insulating material at the point at which it passes through the side or top of the space in which the appliance is installed and, if the side or top is of a combustible material, there must be a clearance of not less than 25 mm between the flue and the combustible material.

        (3)         A flue fitted to an appliance —

            (a)         must not be fitted with a damper; and

            (b)         must have an approved flue terminal located not less than 50 mm away from the outside surface of the marine craft.

810 .         Water or room heaters

        (1)         A gas water heater must not be installed in a marine craft except in the galley or such other place as is approved in each case by an inspector.

        (2)         A gas water heater or a gas room heater —

            (a)         must not be located below the level of the main deck except as approved in each case by an inspector and subject to clause 806; and

            (b)         must be fitted with a flue and a flame safeguard system.

811 .         Cooking appliances

                If a gas cooking appliance is mounted on gimbals —

            (a)         the cooking appliance must be fitted with fiddle rails; and

            (b)         the cooking appliance must be sufficiently clear of surrounding objects and structures to allow for gimbal movement.

812 .         Warnings

                There must be kept in a conspicuous position adjacent to an appliance, or if there is more than one appliance, adjacent to one of the appliances, a legible and clear warning in a permanent form, setting out the following —


Approval of an inspector is required before appliances may be altered.



AustLII: Copyright Policy | Disclaimers | Privacy Policy | Feedback