BUILDING REGULATION 2006 - REG 13AC
Smoke alarms for domestic dwellings
13AC Smoke alarms for domestic dwellings
(1) A smoke alarm must be installed in each bedroom of the domestic dwelling,
in a place that complies with section 13AD .
(2) Each smoke alarm must— (a)
comply with AS 3786–2014; and
(b) contain a photoelectric sensor; and
(c)
not also contain an ionisation sensor; and
(d) be hardwired to the domestic
dwelling’s electricity supply; and
(e) be interconnected to every other
smoke alarm installed in the dwelling.
(3) A smoke alarm (the
"first smoke alarm" ) is interconnected to another smoke alarm if— (a) the
first smoke alarm sounds an alert if the other smoke alarm is activated
because its sensor detects smoke; and
(b) the other smoke alarm sounds an
alert if the first smoke alarm is activated because its sensor detects smoke.
(4) Subsections (1) and (2) do not apply to a sole-occupancy unit in a class 2
building if a smoke detection system that complies with the BCA, specification
E2.2a, clause 4 has been installed in the domestic dwelling.
(5) If the BCA
is inconsistent with this section, this section prevails to the extent of the
inconsistency.