COAL MINING SAFETY AND HEALTH REGULATION 2017 - REG 28

Electrical protection for power outlets for low voltage electrical equipment

28 Electrical protection for power outlets for low voltage electrical equipment

(1) A coal mine’s electrical engineering manager must ensure a single-phase power outlet for low voltage electrical equipment at the mine has—
(a) earth leakage current protection of not more than 30mA sensitivity; or
(b) a device preventing its use by portable electrical equipment.
(2) Subsection (1) does not apply if the power outlet is the only outlet in an isolated electricity supply.
(3) In this section—

"isolated electricity supply" means an electricity supply—
(a) other than the main electricity supply, that is totally insulated from conductive material; or
(b) that is—
(i) supplied with electricity from the main electricity supply; and
(ii) totally isolated from the main electricity supply; and
(iii) totally insulated from earth.