ELECTRICAL SAFETY REGULATION 2013 - REG 245
Further tests during period of registration of system
245 Further tests during period of registration of system
(1) This section applies to a cathodic protection system that is a registered
system.
(2) The owner of the system must perform interference tests on all
foreign structures for the system— (a) when an anode forming part of the
system is replaced; and
(b) if required by the regulator—when the system,
or its method of operation, is changed.
Penalty— Maximum penalty—40
penalty units.
(3) If the system has an immersed anode that is redesigned,
causing the anode to be relocated or to become subject to variation in anode
current distribution, the owner of the system must retest the system to ensure
the potential difference between any 2 accessible points spaced 1m apart in
the water or marine environment is not more than 3V when the system is
energised. Penalty— Maximum penalty—40 penalty units.
(4) If, when
interference tests are being performed, there is a foreign structure for the
system for which interference tests have not previously been performed, the
person must— (a) arrange with the foreign structure owner a mutually
acceptable time for performing the tests; and
(b) allow the foreign structure
owner to observe the performance of the tests.
Penalty— Maximum
penalty for subsection (4) —40 penalty units.