Quality standard for class A, B, C or D recycled water
59 Quality standard for class A, B, C or D recycled water
(1) Recycled water that is to be supplied as class A, B, C or D recycled water
must be tested for the presence of Escherichia coli at the frequency required
under the management plan for the water.
(2) If the quality of the water has
been tested for Escherichia coli for at least 1 year under the management plan
for the water— (a) each month, the samples of water, other than resamples,
taken to test for Escherichia coli during the preceding 1-year period must be
reviewed; and
(b) at least 95% of the samples reviewed must contain less than
the following amounts of Escherichia coli — (i) for class A recycled
water—10 cfu/100mL or MPN/100mL;
(ii) for class B recycled water—100
cfu/100mL or MPN/100mL;
(iii) for class C recycled water—1,000 cfu/100mL or
MPN/100mL;
(iv) for class D recycled water—10,000 cfu/100mL or MPN/100mL.