ELECTRICITY SAFETY (INSTALLATIONS) REGULATIONS 2009 (SR NO 164 OF 2009) - REG 217

Minimum depths of high voltage underground lines and underground lines on public land and on private land not owned or leased by the owner of the line

    (1)     A high voltage underground line, or any underground line on public land or on private land not owned or leased by the owner of the line must not be closer to the surface of the ground than the relevant minimum depth specified in column 2, 3, or 4 of Table 217.

Note

Section 46 of the Act generally prohibits the construction of electric lines on public land unless an exemption applies.

    (2)     Subregulation (1) does not apply to the initial portion of an underground line if the initial portion—

        (a)     is protected by a mechanical cover in accordance with regulation 216(1) ; or

        (b)     is enclosed in a heavy duty non-metallic conduit that complies with AS/NZS 2053; or

        (c)     is enclosed in a medium or heavy galvanised steel tube that complies with AS 1074.

    (3)     Subregulation (1) does not apply to—

        (a)     negative conductors; or

        (b)     those portions of underground lines that are above ground.

TABLE 217—Minimum depths for underground lines from
the surface of the ground

Column 1





Type of underground line Nominal voltage ("U")

Column 2





Directly buried

Column 3

Directly buried and covered with a mechanical cover

Column 4



Buried enclosed in a conduit or pipe

U <1500V direct current

750 mm

600 mm

500 mm

Alternating current U ≤ 1kV

750 mm

600 mm

500 mm

1kV a.c. or 1500V d.c.
< U ≤ 22kV


900 mm


750 mm


750 mm

22kV < U ≤ 66kV

1000 mm

750 mm

750 mm

66kV < U ≤ 220kV

1000 mm

1000 mm

1000 mm