ELECTRICITY SAFETY (INSTALLATIONS) REGULATIONS 2009 (SR NO 164 OF 2009) - REG 225

Minimum distances between aerial lines and buildings or structures

    (1)     An aerial line carrying alternating current at a voltage set out in Row V of Table 225.1 must not, at any time, be closer to a building or structure or part of a building or structure specified in Rows A to D in Column 1 of Table 225.1 than the relevant minimum distance specified for that type of aerial line in Column 2, 3, 4, 5, 6, 7 or 8 for the relevant Row of that Table.

    (2)     An aerial line carrying direct current at a voltage set out in Row V of Table 225.2 must not, at any time, be closer to a building or structure or part of a building or structure specified in Row A to E in Column 1 of Table 225.2 than the relevant minimum distance specified for that type of aerial line in Column 2, 3 or 4 for the relevant Row of that Table.

    (3)     The minimum distances in Rows A, B, C and D of Tables 225.1 and 225.2 do not apply to the connection of an aerial line to a pole, tower or substation.

    (4)     The minimum distances in Rows B, C and D of Tables 225.1 and 225.2 do not apply to—

        (a)     that part of an aerial line close to a building or structure for the purposes of supplying electricity to the building or structure; or

        (b)     low voltage insulated conductors attached to the façade of any building or structure; or

        (c)     high voltage insulated conductors attached to a part of a building or structure on private land that is—

              (i)     not the façade of that building or a part of that building; or

              (ii)     not adjoining a public way or space.

    (5)     Figures 225.1 and 225.2 are for illustrative purposes only and are not intended to be a comprehensive depiction of the situations they illustrate.

Note

Row labels contained in Tables 225.1 and 225.2 correspond with letters shown in figures 225.1 and 225.2.

TABLE 225.1—Minimum distances to parts of buildings or structures from aerial lines carrying alternating current


Minimum distance for type of aerial line and nominal voltage ("U")

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Column 8


Alternating current
aerial line

Insulated with earthed screen

Insulated without earthed screen



Bare or covered




Bare




Bare




Bare




Bare

Row V








Voltage



U>1kV



U>1kV


1kV < U ≤ 33kV


33kV < U ≤ 132kV

132kV < U ≤ 275kV

275kV < U ≤ 330kV

330kV <
U ≤
500kV

Row A








Vertically above those parts of a building or structure normally accessible to persons

2700 mm

3700 mm

4500 mm

5000 mm

6800 mm

8000 mm

9800 mm

Row B








Vertically above those parts of a building or structure not normally accessible to persons but on which a person can stand

100 mm

2700 mm

3700 mm

4500 mm

6000 mm

7000 mm

8000 mm

Row C








In any direction, other than vertically above, from those parts of a building or structure normally accessible to persons, or from any part not normally accessible to persons but on which a person can stand

100 mm

1500 mm

2100 mm

3000 mm

4600 mm

5500 mm

6400 mm

Row D








In any direction from those parts of a building or structure not normally accessible to persons

100 mm

600 mm

1500 mm

2500 mm

3700 mm

4700 mm

6400 mm


TABLE 225.2—Minimum distances to parts of buildings or structures from aerial lines carrying direct current

Column 1

Column 2

Column 3

Column 4


Minimum distance for type of aerial line and nominal voltage ("U")

Row V


U≤ 600V


U≤ 600V

600V < U≤ 1500V


Direct current aerial line


Insulated


Bare

Bare or insulated

Row A




Vertically above those parts of a building or structure normally accessible to persons

2700 mm

3700 mm

4500 mm

Row B




Vertically above those parts of a building or structure not normally accessible to persons but on which a person can stand

100 mm

2700 mm

3700 mm

Row C




In any direction, other than vertically above, from those parts of a building or structure normally accessible to persons or vertically below as described in row E, or from any part not normally accessible to persons but on which a person can stand

100 mm

1500 mm

2100 mm

Row D




In any direction, other than vertically below as described in row E, from those parts of a building or structure not normally accessible to persons

100 mm

600 mm

1500 mm

Column 1

Column 2

Column 3

Column 4


Direct current aerial line


Insulated


Bare

Bare or insulated

Row E




Vertically below those parts of a building or structure erected over a small gauge railway or tramway system

100 mm

300 mm

300 mm

09-164sr01.jpg