ELECTRICITY SAFETY (INSTALLATIONS) REGULATIONS 2009 (SR NO 164 OF 2009) - REG 223

Minimum distances between aerial lines and the ground or water

    (1)     A low voltage aerial line on public land or on private land not owned or leased by the owner of the line or a d.c. traction conductor must not, at any time, be closer to—

        (a)     the ground; or

        (b)     the surface of any water that is not accessible to boats with masts—

than the relevant minimum distance specified in Column 2, 3 or 4 of Table 223.1 for the location of the aerial line specified in Column 1 of that Table.

    (2)     A high voltage aerial line at the location specified in Column 1 of Table 223.2 must not, at any time, be closer to—

        (a)     the ground; or

        (b)     the surface of any water that is not accessible to boats with masts—

than the relevant minimum distance specified for those types of aerial lines in Column 2, 3 or 4 of Table 223.2 opposite those lines.

    (3)     An aerial line must not, at any time, be closer than 13 500 millimetres to the surface of any water that is accessible to boats with masts.

    (4)     The minimum distances specified in Column 2, 3, or 4 of Tables 223.1 and 223.2 do not apply to a part of an aerial line that is within a substation.

    (5)     In Tables 223.1 and 223.2—

"arterial road" means a road designated as an arterial road in the VicRoads Country Street Directory;

"collector road" means a road designated as a collector road in the Melways Street Directory but does not include such a road that is also—

        (a)     an over-dimensional route; or

        (b)     a relevant docks road;

"freeway" means a road designated as a freeway in—

        (a)     the Melways Street Directory; or

        (b)     the VicRoads Country Street Directory;

"major road" means a road designated as a major road in the Melways Street Directory but does not include such a road that is also—

        (a)     an over-dimensional route; or

        (b)     a relevant docks road;

"over-dimensional route" means a road designated as an over-dimensional route in the Melways Street Directory;
r. 223

"primary state arterial road "means a road designated as a primary state arterial road in the Melways Street Directory;

"road" means a road shown in—

        (a)     the Melways Street Directory; or

        (b)     VicRoads Country Street Directory;

"relevant docks road" means any of the following roads or streets—

        (a)     Anderson Road, West Melbourne;

        (b)     Appleton Dock Road, West Melbourne;

        (c)     Coode Road, West Melbourne;

        (d)     Cowper Street, Footscray;

        (e)     Dock Link Road, West Melbourne;

        (f)     Gibbons Street, West Melbourne;

        (g)     MacKenzie Road, West Melbourne;

        (h)     Phillipps Road, West Melbourne;

"secondary state arterial road" means a road designated as a secondary state arterial road in the Melways Street Directory but does not include such a road that is also an over-dimensional route;

"tollway" means a road designated as a tollway in the Melways Street Directory.

TABLE 223.1—Minimum distances to the ground or water surface
from low voltage aerial lines on public land or within an
easement on private land or traction conductors


Type of aerial line

Column 1


Location of aerial line

Column 2


Bare live conductors

Column 3


Insulated live conductors

Column 4

Direct current traction conductors

Minimum distance to ground or surface of water

Over a 2000 mm wide strip in the centre of each carriageway of a road

5500 mm

5500 mm

5000 mm

Over any other part of a freeway, tollway, primary state arterial road, arterial road, overdimensional route or relevant docks road

5500 mm

5500 mm

5000 mm

Over any other part of a secondary state arterial road, major road or collector road

5500 mm

4900 mm

5000 mm

Over any other part of any other road

5500 mm

4600 mm

5000 mm

Over any part of a driveway

5500 mm

4600 mm

5000 mm

Over any other ground traversable by vehicles (other than a road)

5500 mm

4600 mm

5000 mm

At the connection to a building or structure (excluding a pole)

Not permitted

3000 mm

Not permitted

Over the surface of any water not accessible to boats with masts

4500 mm

4500 mm

4500 mm

Elsewhere

5000 mm

3000 mm

4500 mm

TABLE 223.2—Minimum distances to the ground or water surface from high voltage aerial lines


Minimum distance

Column 1





Type of aerial line
Nominal voltage ("U")

Column 2





Carriageway of roads

Column 3


Ground traversable by vehicles (other than a road)

Column 4

Other ground or the surface of any water not accessible to boats with masts

Alternating current insulated with earthed screen U > 1kV

5500 mm

5500 mm

4500 mm

Alternating current insulated without an earthed screen U > 1kV

6000 mm

5500 mm

4500 mm

Bare or covered

1kV a.c or 1500V d.c.
< U ≤ 33kV

6700 mm

5500 mm

5000 mm

Bare or covered

33kV < U ≤ 132kV

6700 mm

6700 mm

5500 mm




Bare or covered

132kV < U ≤ 275kV

8700 mm

7500 mm

6700 mm

Bare or covered

275kV < U ≤ 330kV

9700 mm

8000 mm

6700 mm

330kV < U ≤ 500kV

11 400 mm

10 700 mm

10 700 mm