ELECTRICITY SAFETY (INSTALLATIONS) REGULATIONS 2009 (SR NO 164 OF 2009) - REG 227

Minimum distances between aerial lines and parts of small gauge tram systems

An aerial line carrying alternating current at a voltage set out in Column 1 of Table 227 must not, at any time, be closer to a part of a small gauge tram system specified in Row A in Column 2, 3 or 4 of the Table than the relevant minimum distance specified for that part in Column 2, 3 or 4 of that Table opposite the corresponding voltage.

TABLE 227—Minimum distances to parts of small gauge tramway systems from aerial lines carrying alternating current


Column 1

Column 2

Column 3

Column 4



Minimum distance from part of a small gauge tramway system

Row A



Alternating current aerial line Nominal voltage ("U")





Above track



From d.c. traction conductors

From d.c. traction conductor wire/cable supports

Row B

U ≤ 1kV

7000 mm

600 mm

2700 mm

Row C

1kV < U≤ 22kV

8200 mm

1200 mm

3700 mm

Row D

22kV < U≤ 66kV

8200 mm

1800 mm

4600 mm

Row E

66kV < U≤ 132kV

8200 mm

2100 mm

4600 mm

Row F

132kV < U≤ 220kV

9000 mm

3000 mm

5500 mm

Row G

220kV < U≤ 330kV

9800 mm

4000 mm

6400 mm

Row H

330kV < U≤ 500kV

11 300 mm

5500 mm

7900 mm