ELECTRICITY SAFETY (INSTALLATIONS) REGULATIONS 2009 (SR NO 164 OF 2009) - REG 227
Minimum distances between aerial lines and parts of small gauge tram systems
An aerial line carrying alternating current at a voltage set out in Column 1
of Table 227 must not, at any time, be closer to a part of a small gauge tram
system specified in Row A in Column 2, 3 or 4 of the Table than the
relevant minimum distance specified for that part in Column 2, 3 or 4 of that
Table opposite the corresponding voltage.
TABLE 227—Minimum distances to parts of small gauge tramway systems from
aerial lines carrying alternating current
|
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
|
Minimum distance from part of a small gauge tramway system |
Row A |
Alternating current aerial line Nominal voltage ("U") |
Above track |
From d.c. traction conductors |
From d.c. traction conductor wire/cable supports |
Row B |
U ≤ 1kV |
7000 mm |
600 mm |
2700 mm |
Row C |
1kV < U≤ 22kV |
8200 mm |
1200 mm |
3700 mm |
Row D |
22kV < U≤ 66kV |
8200 mm |
1800 mm |
4600 mm |
Row E |
66kV < U≤ 132kV |
8200 mm |
2100 mm |
4600 mm |
Row F |
132kV < U≤ 220kV |
9000 mm |
3000 mm |
5500 mm |
Row G |
220kV < U≤ 330kV |
9800 mm |
4000 mm |
6400 mm |
Row H |
330kV < U≤ 500kV |
11 300 mm |
5500 mm |
7900 mm |