Victorian Numbered Regulations

[Index] [Table] [Search] [Search this Regulation] [Notes] [Noteup] [Previous] [Next] [Download] [Help]

ELECTRICITY SAFETY (INSTALLATIONS) REGULATIONS 2009 (SR NO 164 OF 2009) - REG 228

Minimum distances between aerial lines

    (1)     An aerial line set out in Rows C to G Column 1 or 2 of Table 228 that forms part of—

        (a)     a high voltage electrical installation; or

        (b)     the supply network of a small gauge railway—

must not, at any time, be closer to an aerial line specified in the same Row as that line than the relevant minimum distance specified in Column 3, 4 or 5 for the relevant Row of the Table for the location of the aerial line specified in Row B in those columns.

    (2)     The nominal voltage of the lower circuit of an aerial line must not be greater than the nominal voltage of the upper circuit of an aerial line.

    (3)     A d.c. traction conductor for a small gauge tram system must not, at any time, cross an electrolysis drainage cable, unless the conductor and the cable are attached to a common pole or support.

TABLE 228—Minimum distances between aerial lines


Column 1

Column 2

Column 3

Column 4

Column 5

Row A

Type and nominal voltage ("U")


Minimum distance

Row B







Upper circuit







Lower circuit



Between the aerial line spans. Circuits on the same pole line

Between the points where the aerial lines are attached to a common pole or support


Between the aerial line spans. Circuits crossing not on same pole line

Row C

Low voltage alternating current aerial line

d.c. traction conductor

U≤ 1500V

1000 mm

1000 mm

1000 mm

Row D

d.c. traction conductor

U≤ 1500V

Electrolysis drainage cable

1000 mm

1000 mm

Not permitted

Row E

d.c. traction conductor
U≤ 1500V

Other cable system

1000 mm

1000 mm

1000 mm

Row F

Alternating current aerial line

U > 1kV
U ≤ 33kV

Alternating current aerial line

U ≤ 33kV

1200 mm

1200 mm

750 mm

Row G

Alternating current aerial line

U > 33kV
U ≤ 66kV

Alternating current aerial line

U ≤ 66kV

1800 mm

1800 mm

1200 mm



AustLII: Copyright Policy | Disclaimers | Privacy Policy | Feedback