PUBLIC HEALTH AND WELLBEING REGULATIONS 2019 (SR NO 135 OF 2019) - REG 69

Disinfection, cleaning and re-disinfection of cooling tower system

Immediately prior to a cooling tower system being put into operation for the first time, or following any shut down period of greater than one month and at intervals not exceeding 6 months, a responsible person must ensure that—

        (a)     a chlorine-compatible bio-dispersant is added to the recirculating water; and

        (b)     the recirculating water is disinfected; and

        (c)     the interior of each cooling tower in the cooling tower system is cleaned; and

        (d)     the recirculating water is re-disinfected.

Penalty:     20 penalty units.