Victorian Numbered Regulations

[Index] [Table] [Search] [Search this Regulation] [Notes] [Noteup] [Previous] [Next] [Download] [Help]

PUBLIC HEALTH AND WELLBEING REGULATIONS 2019 (SR NO 135 OF 2019) - REG 70

Routine service and testing obligations

    (1)     A responsible person must ensure that a cooling tower system is serviced at least once each month to determine whether the cooling tower system is operating without defects.

Penalty:     20 penalty units.

    (2)     A responsible person must ensure that at least once each month a sample of recirculating water is taken and provided to a laboratory to determine the heterotrophic colony count of the recirculating water.

Penalty:     20 penalty units.

    (3)     A responsible person must ensure that at least once every 3 months a sample of recirculating water is taken and provided to a laboratory to test for Legionella.

Penalty:     20 penalty units.